| Availability: | |
|---|---|
| Quantity: | |
Transformer Isolation Design: Built specifically for 48V low-voltage batteries, the internal transformer isolation design ensures ultimate electrical safety and system stability.
Max 240A Current Processing: Delivers up to 240A of charging/discharging current to manage dynamic commercial or large residential loads smoothly.
Interactive IP66 Touchscreen: Features a full-color touch LCD for rapid diagnostics, enclosed in an IP66 rugged body suitable for challenging environments.
AC Coupling Support: Readily retrofits existing three-phase solar systems into modern, battery-backed hybrid solutions.
Generator Energy Capture: Supports diesel generator inputs to capture excess electricity, reducing generator runtime and saving fuel.
Time-of-Use Management: 6 programmable time periods enable intelligent battery management to reduce grid reliance during peak rate hours.
Up to 10 Units Parallel: Scale your three-phase power easily by connecting up to 10 units in parallel for demanding on-grid and off-grid operations.
MODEL | LD06H-TM-6K-EP-D | LD06H-TM-8K-EP-D | LD06H-TM-10K-EP-D | LD06H-TM-12K-EP-D |
Battery Input Data | ||||
Battery Type | Lead-acid or Lithium-ion | |||
Battery Voltage Range (V) | 40-60 | |||
Max. Charging Current (A) | 135 | 190 | 210 | 240 |
Max. Discharging Current (A) | 135 | 190 | 210 | 240 |
Charging Strategy for Li-lon Battery | Self-adaption to BMS | |||
Number of Battery Input | 1 | |||
String Input Data | ||||
Max. PV access Power(W) | 12000 | 16000 | 20000 | 24000 |
Max. PV Input Power(W) | 9600 | 12800 | 16000 | 19200 |
Max. PV Input Voltage(V) | 800 | |||
Start-up Voltage (V) | 160 | |||
PV Input Voltage Range(V) | 160-800 | |||
MPPT Voltage Range(V) | 200-650 | |||
Full Load MPPT Voltage Range(V) | 260-650 | 360-650 | ||
Rated PV Input Voltage(V) | 550 | |||
Max. Operating PV Input Current(A) | 20+20 | 26+26 | ||
Max. Input Short-Circuit Current(A) | 30+30 | 39+39 | ||
No. of MPP Trackers/No. of Strings MPP Tracker | 2/1+1 | 2/2+2 | ||
Max. Inverter Backfeed Current to The Array | 0 | |||
Input Data | ||||
Rated AC Input/Output Active Power(W) | 6000 | 8000 | 10000 | 12000 |
Max. AC Input/Output Apparent Power(VA) | 6600 | 8800 | 1 1000 | 13200 |
Peak Power(off grid)(W) | 2 times of rated power, 10s | |||
Rated AC Input/Output Current(A) | 9.1/8.7 | 12.2/11.6 | 15.2/14.5 | 18.2/17.4 |
Max. Rated AC Input/Output Current(A) | 10/9.6 | 13.4/12.8 | 16.7/16 | 20/19.2 |
Max. Continuous AC Passthrough(grid to load)(A) | 45 | |||
Max. Output Fault Current(A) | 20 | 26.8 | 33.4 | 40 |
Max. Output Overcurrent Protection(A) | 65 | |||
Rated Input/Output Voltage/Range(V) | 220/380V,230/400V 0.85Un-1.1Un | |||
Grid Connection Form | 3L+N+PE | |||
Rated Input Grid Frequency/Range | 50Hz/45Hz-55Hz 60Hz/55Hz-65Hz | |||
Power Factor Adjustment Range | 0.8 leading-0.8 lagging | |||
Total Harmonic Distortion(THDi) | <3% (of nominal power) | |||
DC Injection Current | <0.5% In | |||
Efficiency | ||||
Max. Efficiency | 97.60% | |||
Euro Efficiency | 97.00% | |||
MPPT Efficiency | >99.0% | |||
Equipment Protection | ||||
DC Polarity Reverse Connection Protection | Yes | |||
AC Output Overcurrent Protection | Yes | |||
AC Output Overvoltage Protection | Yes | |||
AC Output Short Circuit Protection | Yes | |||
Thermal Protection | Yes | |||
DC Terminal Insulation Impedance Monitoring | Yes | |||
DC Component Monitoring | Yes | |||
Ground Fault Current Monitoring | Yes | |||
Arc fault circuit interrupter(AFCI) | Optional | |||
Power Network Monitoring | Yes | |||
Island Protection Monitoring | Yes | |||
Earth Fault Detection | Yes | |||
DC Input Switch | Yes | |||
Overvoltage Load Drop Protection | Yes | |||
Residual Current (RCD) Detection | Yes | |||
Surge Protection Level | Type II(DC) / Type II(AC) | |||
Interface | ||||
Display | LCD+LED | |||
Communication Interface | RS232, RS485, CAN | |||
Monitor Mode | GPRS/WIFI/Bluetooth/4G/LAN(optional) | |||
General Data | ||||
Operating Temperature Range | -40 to +60℃, >45℃ Derating | |||
Permissible Ambient Humidity | 0-100% | |||
Permissible Altitude | 3000m | |||
Noise(dB) | ≤55 dB | |||
Ingress Protection(IP) Rating | IP 66 | |||
Inverter Topology | Non-Isolated | |||
Over Voltage Category | OVC II(DC), OVC III(AC) | |||
Weight(kg) | 35 | |||
Cabinet size(mm)(W×H×D) | 350×660×260 (Excluding connectors and brackets) | |||
Warranty | 5 Years (10 Years Optional) | |||
Type of Cooling | Intelligent Air Cooling | |||
Grid Regulation | IEC 61727,IEC 62116,EN 50549 | |||